High Power Density, High Efficiency Single Phase Transformer-less Photovoltaic String Inverters
Description
Two major challenges in the transformer-less, single-phase PV string inverters are common mode leakage currents and double-line-frequency power decoupling. In the proposed doubly-grounded inverter topology with innovative active-power-decoupling approach, both of these issues are simultaneously addressed. The topology allows the PV negative terminal to be directly connected to the neutral, thereby eliminating the common-mode ground-currents. The decoupling capacitance requirement is minimized by a dynamically-variable dc-link with large voltage swing, allowing an all-film-capacitor implementation. Furthermore, the use of wide-bandgap devices enables the converter operation at higher switching frequency, resulting in smaller magnetic components. The operating principles, design and optimization, and control methods are explained in detail, and compared with other transformer-less, active-decoupling topologies. A 3 kVA, 100 kHz single-phase hardware prototype at 400 V dc nominal input and 240 V ac output has been developed using SiC MOSFETs with only 45 μF/1100 V dc-link capacitance. The proposed doubly-grounded topology is then extended for split-phase PV inverter application which results in significant reduction in both the peak and RMS values of the boost stage inductor current and allows for easy design of zero voltage transition. A topological enhancement involving T-type dc-ac stage is also developed which takes advantage of the three-level switching states with reduced voltage stress on the main switches, lower switching loss and almost halved inductor current ripple.
In addition, this thesis also proposed two new schemes to improve the efficiency of conventional H-bridge inverter topology. The first scheme is to add an auxiliary zero-voltage-transition (ZVT) circuit to realize zero-voltage-switching (ZVS) for all the main switches and inherent zero-current-switching (ZCS) for the auxiliary switches. The advantages include the provision to implement zero state modulation schemes to decrease the inductor current THD, naturally adaptive auxiliary inductor current and elimination of need for large balancing capacitors. The second proposed scheme improves the system efficiency while still meeting a given THD requirement by implementing variable instantaneous switching frequency within a line frequency cycle. This scheme aims at minimizing the combined switching loss and inductor core loss by including different characteristics of the losses relative to the instantaneous switching frequency in the optimization process.
In addition, this thesis also proposed two new schemes to improve the efficiency of conventional H-bridge inverter topology. The first scheme is to add an auxiliary zero-voltage-transition (ZVT) circuit to realize zero-voltage-switching (ZVS) for all the main switches and inherent zero-current-switching (ZCS) for the auxiliary switches. The advantages include the provision to implement zero state modulation schemes to decrease the inductor current THD, naturally adaptive auxiliary inductor current and elimination of need for large balancing capacitors. The second proposed scheme improves the system efficiency while still meeting a given THD requirement by implementing variable instantaneous switching frequency within a line frequency cycle. This scheme aims at minimizing the combined switching loss and inductor core loss by including different characteristics of the losses relative to the instantaneous switching frequency in the optimization process.
Date Created
The date the item was original created (prior to any relationship with the ASU Digital Repositories.)
2017
Agent
- Author (aut): Xia, Yinglai
- Thesis advisor (ths): Ayyanar, Raja
- Committee member: Karady, George G.
- Committee member: Lei, Qin
- Committee member: Qin, Jiangchao
- Publisher (pbl): Arizona State University