Advancing performance of passive downdraft cooling towers
Description
Passive cooling techniques, specifically passive downdraft cooling (PDC), have proven to be a solution that can address issues associated with air conditioning (AC). Globally, over 100 buildings have integrated PDC in its different forms, most of which use direct evaporative cooling. Even though all surveyed buildings were energy efficient and cost-effective and most surveyed buildings were thermally comfortable, application of PDC remains limited. This study aims to advance performance of the single stage passive downdraft evaporative cooling tower (PDECT), and expand its applicability beyond the hot dry conditions where it is typically used, by designing and testing a multi-stage passive and hybrid downdraft cooling tower (PHDCT). Experimental evaluation on half-scale prototypes of these towers was conducted in Tempe, Arizona, during the hot dry and hot humid days of Summer, 2017. Ambient air dry-bulb temperatures ranged between 73.0°F with 82.9 percent coincident relative humidity, and 123.4°F with 7.8 percent coincident relative humidity. Cooling systems in both towers were operated simultaneously to evaluate performance under identical conditions.
Results indicated that the hybrid tower outperformed the single stage tower under all ambient conditions and that towers site water consumption was at least 2 times lower than source water required by electric powered AC. Under hot dry conditions, the single stage tower produced average temperature drops of 35°F (5°F higher than what was reported in the literature), average air velocities of 200 fpm, and average cooling capacities of 4 tons. Furthermore, the hybrid tower produced average temperature drops of 45°F (50°F in certain operation modes), average air velocities of 160 fpm, and average cooling capacities exceeding 4 tons. Under hot humid conditions, temperature drops from the single stage tower were limited to the ambient air wet-bulb temperatures whereas drops continued beyond the wet-bulb in the hybrid tower, resulting in 60 percent decline in the former’s cooling capacity while maintaining the capacity of the latter. The outcomes from this study will act as an incentive for designers to consider incorporating PDC into their designs as a viable replacement/supplement to AC; thus, reducing the impact of the built environment on the natural environment.
Results indicated that the hybrid tower outperformed the single stage tower under all ambient conditions and that towers site water consumption was at least 2 times lower than source water required by electric powered AC. Under hot dry conditions, the single stage tower produced average temperature drops of 35°F (5°F higher than what was reported in the literature), average air velocities of 200 fpm, and average cooling capacities of 4 tons. Furthermore, the hybrid tower produced average temperature drops of 45°F (50°F in certain operation modes), average air velocities of 160 fpm, and average cooling capacities exceeding 4 tons. Under hot humid conditions, temperature drops from the single stage tower were limited to the ambient air wet-bulb temperatures whereas drops continued beyond the wet-bulb in the hybrid tower, resulting in 60 percent decline in the former’s cooling capacity while maintaining the capacity of the latter. The outcomes from this study will act as an incentive for designers to consider incorporating PDC into their designs as a viable replacement/supplement to AC; thus, reducing the impact of the built environment on the natural environment.
Date Created
2017
Contributors
- Al-Hassawi, Omar Dhia Sadulah (Author)
- Bryan, Harvey (Thesis advisor)
- Reddy, T Agami (Committee member)
- Chalfoun, Nader (Committee member)
- Arizona State University (Publisher)
Topical Subject
- Sustainability
- Architectural engineering
- Architecture
- Multi-stage Downdraft Cooling Tower
- Passive and Hybrid Downdraft Cooling Towers
- Passive Cooling
- Passive Downdraft Evaporative Cooling Tower
- Passive Downdraught Cooling
- Single Stage Downdraft Cooling Tower
- Cooling towers
- Air conditioning
- Evaporative cooling
- Renewable energy sources
Resource Type
Extent
xv, 210 pages : illustrations (some color)
Language
eng
Copyright Statement
In Copyright
Primary Member of
Peer-reviewed
No
Open Access
No
Handle
https://hdl.handle.net/2286/R.I.46229
Statement of Responsibility
by Omar Dhia Sadulah Al-Hassawi
Description Source
Viewed on May 14, 2020
Level of coding
full
Note
thesis
Partial requirement for: Ph.D., Arizona State University, 2017
bibliography
Includes bibliographical references (pages 159-167)
Field of study: Architecture
System Created
- 2018-02-01 07:03:35
System Modified
- 2021-08-26 09:47:01
- 3 years 2 months ago
Additional Formats