Description
On-line dynamic security assessment (DSA) analysis has been developed and applied in several power dispatching control centers. Existing applications of DSA systems are limited by the assumption of the present system operating conditions and computational speeds. To overcome these obstacles, this research developed a novel two-stage DSA system to provide periodic security prediction in real time. The major contribution of this research is to develop an open source on-line DSA system incorporated with Phasor Measurement Unit (PMU) data and forecast load. The pre-fault prediction of the system can provide more accurate assessment of the system and minimize the disadvantage of a low computational speed of time domain simulation.
This Thesis describes the development of the novel two-stage on-line DSA scheme using phasor measurement and load forecasting data. The computational scheme of the new system determines the steady state stability and identifies endangerments in a small time frame near real time. The new on-line DSA system will periodically examine system status and predict system endangerments in the near future every 30 minutes. System real-time operating conditions will be determined by state estimation using phasor measurement data. The assessment of transient stability is carried out by running the time-domain simulation using a forecast working point as the initial condition. The forecast operating point is calculated by DC optimal power flow based on forecast load.
This Thesis describes the development of the novel two-stage on-line DSA scheme using phasor measurement and load forecasting data. The computational scheme of the new system determines the steady state stability and identifies endangerments in a small time frame near real time. The new on-line DSA system will periodically examine system status and predict system endangerments in the near future every 30 minutes. System real-time operating conditions will be determined by state estimation using phasor measurement data. The assessment of transient stability is carried out by running the time-domain simulation using a forecast working point as the initial condition. The forecast operating point is calculated by DC optimal power flow based on forecast load.
Details
Title
- Online Dynamic Security Assessment Using Phasor Measurement Unit and Forecasted Load
Contributors
- Wang, Qiushi (Author)
- Karady, George G. (Thesis advisor)
- Pal, Anamitra (Committee member)
- Holbert, Keith E. (Committee member)
- Arizona State University (Publisher)
Date Created
The date the item was original created (prior to any relationship with the ASU Digital Repositories.)
2017
Subjects
Resource Type
Collections this item is in
Note